Control Output

The Control Output is the analog control signal voltage supplied by the RMC to drive the amplifier, valve, or drive for the system to be controlled.

Depending on the hardware, the Control Output may be voltage with a range of -10 V to +10 V, or current with a range of -20 mA to +20 mA. Voltage output may be converted to current (up to ±200 mA) via Delta's VC2124 voltage-to-current converter.

The modules listed below have a physical Control Output. The Control Output is labeled Drive or Drv on the RMC150 modules.

Module

±10 V

4-20 mA

±20 mA

RMC75

AA1, AA2

 

 

MA1, MA2

 

 

QA1, QA2

 

 

RMC150

Analog (H)

 

 

Analog (G)

 

 

MDT (M)

 

 

Quad (Q)

 

 

Resolver (R)

 

 

SSI (S)

 

 

RMC200

CA4

CV8

 

 

U14

Configuring the Control Output

RMC75/150

The user can configure the polarity of this output with the Invert Output Polarity parameter. To invert the polarity of the Control Output, set this bit.

 

RMC200

The user has great flexibility in configuring the range of the Control Output. See the Output Type axis parameter topic for details.

Specifications

For specifications, refer to the topic of the specific module containing the Control Output.

 

See Also

RMC75 AA Wiring | RMC75 A Wiring | RMC75 QA Wiring | RMC150 Control Output (Drive) Wiring | RMC200 CA4 Wiring | RMC200 CV8 Wiring | RMC200 U14 Wiring


Send comments on this topic.

Copyright © 2024 Delta Computer Systems, Inc. dba Delta Motion