CV8 Module (RMC200)

8 Voltage Outputs, with 8 Discrete I/O

The CV8 module for the RMC200 provides 8 voltage outputs intended for controlling an actuator. The module includes 8 discrete I/O that can be individually configured as general-purpose inputs, general-purpose outputs, Fault Inputs, or Enable Outputs.

Features

Part Number

The part number of the CV8 module is R200-CV8.

Setting Up the CV8 Module

Wiring

See CV8 Wiring.

Axis Definitions

In order to use a CV8 analog output, it must be assigned to an RMC internal software axis, via the Axis Definitions Dialog.

Output Parameters

After a CV8 analog output has been assigned to an axis, the following axis parameters must be configured:

Specifications

General

 

Weight

397 g + 26 g (2 connectors)

Control Output (8 per module)

Range

± 10 V @ 5 mA (2000 Ω or greater load)

Tolerance at full output

± 5 mV at 10 V

Resolution

18 bits

Hardware Output Filter

First-order filter, time constant 75 μsec

Functional Isolation

500 VAC

Overload protection

Continuous short to common

Overvoltage protection

Outputs are protected by clamp diodes

Discrete Outputs (up to 8 per module)

Output type

Solid State Relay, individually isolated

Logic polarity

User selectable to Active Open or Active Closed

Functional Isolation

500 VAC

Rated voltage

max ±30 V (DC or peak AC voltage)

Maximum current

±75 mA

Maximum propagation delay

2.5 ms

Closed

Low impedance (12 W maximum)

Open

High impedance (<25 nA leakage current at 30 V)

Discrete Inputs (up to 8 per module)

Input characteristics

12-24 Vdc; polarity independent, individually isolated

Logic polarity

User selectable to Active Input “High” or Active Input “Low”
(Open when module not powered)

Functional Isolation

500 VAC

Input “High” range

9 to 26.4 Vdc (polarity independent),
3 mA maximum

Input “Low” range

0 to 5 Vdc (polarity independent), <1 mA

Maximum propagation delay

100 ms Off to On

750 ms On to Off (open collector drive)

Power

Max Power Dissipation

2.0 W

LEDs

Light Bar

State

Description

Off

No power to the RMC200 or the module was not inserted when the RMC200 powered up.

Blue

The module was recognized at power-up.

 

Control Output LEDs: Out0 .. Out7

State

Description

Off

Not assigned

The output is not assigned to an axis.

Green

Operating normally

The axis is operating normally with no latched errors.

Red

Error

The axis has at least one error bit set that has halted the axis.

Amber

Simulate mode

The axis is in simulate mode.

 

Discrete I/O LEDs: D0 .. D7

State

Description

Off

I/O point is off

If this I/O point is configured as an input, then the input is currently low. If this I/O point is configured as an output, then the output is currently open.

Orange

Input is on

This I/O point is configured as an input, and the input is currently high.

Yellow

Output is on

This I/O point is configured as an output, and the output is currently closed.

 

 

See Also

RMC200 Overview | CV8 Wiring