This topic describes how to configure the Discrete IO on the RMC. Each discrete I/O on the RMC can be configured as described below:
Basic Configuration
To configure Discrete I/O, open the Discrete I/O Configuration window first. Then, you can do any of the actions listed below. To apply the changes to the RMC, right-click the Programming node in the Project pane, and click Download Programs to Controller.
Action |
Instructions |
Basic Configuration Options |
|
Configure I/O as Input or Output |
Available only on discrete I/O modules with configurable I/O. In the Type column, choose Input or Output. |
Assign a Tag Name to the I/O |
To assign a tag name to an I/O, type a name in the Tag Name column. Tag names are limited to 64 characters. Tip:
|
Add a Description |
In the Description column, add a description of the I/O point for your own reference. |
Advanced Configuration Options |
|
Set the PROGRAM State for Outputs |
To assign the state of an output when the RMC enters or starts up in PROGRAM mode, in the PROGRAM State column, choose the desired option:
|
Set the FAULT State for Outputs |
The Fault State defines the state of the output in the following conditions:
Options:
|
Defining a RUN/PROGRAM Input (RMC75/150) or
Defingin a RUN/Disable Input (RMC200) |
To assign a discrete input to control the RMC RUN/PROGRAM/Disable mode:
For the RMC75 and RMC150, when the discrete input transitions from low to high, the RMC will enter RUN mode. When the input transitions from high to low, the RMC will enter PROGRAM mode. For the RMC200, When the discrete input transitions from low to high, the RMC will enter RUN mode. When the input is low, the RMC will be in Disabled mode. |
See Also
Copyright © 2024 Delta Computer Systems, Inc. dba Delta Motion