Custom Feedback Auto-Fault Mode

Type:

Axis Parameter Register Bit Parameter

Address:

RMC75:

Primary Input: %MDn.8/0-3, where n = 12 + the axis number

Secondary Input: %MDn.26/0-3, where n = 12 + the axis number

RMC150:

Primary Input: %MDn.8/0-3, where n = 24 + the axis number

Secondary Input: %MDn.26/0-3, where n = 24 + the axis number

RMC200:

Primary Input: %MDn.59/0-3, where n = 24 + the axis number

Secondary Input: %MDn.119/0-3, where n = 24 + the axis number

System Tag:

Secondary Input: _Axis[n].CustomFBConfig.AutoFault

Primary Input: _Axis[n].SecCustomFBConfig.AutoFault

where n is the axis number

How to Find:

Axes Parameters Pane, Setup tab: Feedback

Data Type:

Bits - see below

Range:

Missed Update (0), PROGRAM Mode (1), Disabled (2)

Default Value:

Missed Update (0)

Description

This parameter is valid only on axes with custom feedback on the primary and/or secondary input. This parameter provides options to automatically set the No Transducer or Prs/Frc No Transducer error bit. The following options are available:

If the Custom Counts register is not written to in a given loop time, the No Transducer error will be set. This is the preferred mode for most applications. In this mode, you should make sure that the Custom Counts register is written to each loop time.

If the controller is in PROGRAM mode, the No Transducer error will be set. This mode may be useful in situations where you do not need to update the Custom Counts very often, but you do wish to halt the axis if the program that updates the Custom Counts is stopped due to the controller entering PROGRAM mode.

The No Transducer error will not be set by any of the above options. In this mode, the updating of the Custom Counts register is not monitored in any way. This could be used in cases where the Custom Counts register is being modified from an external device, such as a PLC.

 

The No Transducer Error bit can still be set by using the No Transducer and Secondary No Transducer bits in the Custom Error Bits register. Additionally, if the Custom Counts is NaN, INf, -Inf, the No Transducer error bit will also be set.

Format Details

The Custom Feedback Auto-Fault Mode is selected with bits 0-3. These bits correspond to the Auto-Fault Mode as shown in the following table:

Bit 3

Bit 2

Bit 1

Bit 0

Value

Auto-Fault Mode

0

0

0

0

0

Missed Update

0

0

0

1

1

PROGRAM Mode

0

0

1

0

2

Disabled

See the Custom Feedback Configuration Register for details about the register containing these bits.

 

 

See Also

Custom Feedback | Custom Feedback Configuration Register