The RMC75S combines multiple communication protocols with RS-232 and RS-485 transceiver options to form a versatile and industrial-hardened communication platform. The RS-232 option provides full-duplex point-to-point communications, while RS-485 allows half-duplex multi-drop networking with up to 128 RMC75s.
Due to limited throughput of serial communications, the RMC75S is best suited for applications where time-critical machine control functions related to motion are implemented in the RMC75S using the User Programs. The serial communications is fine for low-bandwidth monitoring or modifications to the RMC75S parameters or User Programs. In applications where higher throughput is necessary, consider the RMC75E Ethernet module.
Features
One serial RS-232 or RS-485 Communications port
One serial RS-232 Monitor Port
Supported Protocols
Allen-Bradley DF1 (Full- and Half-duplex)
Modbus/RTU
Mitsubishi Bidirectional Protocol
Part Number
The part numbers of the RMC75S is RMC75S. Like all RMC75 CPU modules, the RMC75S can only be ordered with an axis module.
For example, RMC75S-QA2 is an RMC75S with a two-axis QA2 module.
Specifications
General |
|
Weight |
245 g + 16 g (connector) |
Serial Interface |
|
Transceivers |
User-selectable: RS-232, RS-485 |
Baud Rates |
9600, 19200, 38400, 57600, 115200 baud |
Stop Bits |
1 or 2 |
Data Length |
8 bits |
Parity |
None, Odd, or Even |
Isolation |
500 VAC |
Electrostatic Discharge (ESD) Protection |
15 kV |
RS-232 Interface |
|
Type |
Single-Ended |
Connector |
DB-9 Male |
Communication Distance |
50 ft (12 m) |
Network Type |
Point-to-Point |
RS-485 Interface |
|
Type |
Differential |
Connector |
5-pin Terminal Block |
Communication Distance |
4000 ft (1200 m) |
Network Type |
RS-485: Point-to-Point or Multi-drop up to 128 nodes |
RS-485 Input Impedance |
48 kΩ (1/4 unit load) |
Biasing |
User selectable |
Termination |
120 Ω user selectable |
RS-232 Monitor Port |
|
Connector |
DB-9 Male |
Cable |
Null modem |
Protocol |
Allen-Bradley DF1 Full-Duplex, with CRC error detection |
Settings |
38400 baud, 8 data bits, no parity, 1 stop bit, no handshaking |
LEDs
Controller LED
This bi-color (red/green) LED has the following states:
State |
Description |
Steady Off |
No power. |
Steady Green |
RUN Mode |
Flashing Green (Slow) |
PROGRAM Mode |
Flashing Green (Fast) |
Updating Flash or a controller restart is pending. |
Flashing Red |
The device is in the loader. This should occur briefly when the controller is powered up. If this occurs during normal operation, an error has occurred in the controller and it must be reset. Cycle power to the RMC75 to reset it. Causes:
|
Steady Red |
Non-Recoverable major fault. That is, the module cannot boot at all, not even into the loader. The module will likely need to be shipped back to Delta for repair. Some things to try to get it into the Loader (to be done at the direction of technical support) include removing all expansion and axis modules, and setting the Force to Loader jumper under the axis module. |
Communication LEDs
These LEDS are located below the Controller LED on a gray background.
Transmit
LED
This LED reflects when data is being transmitted on the second serial port
(RS-232/485).
State |
Description |
Steady Off |
No power or no data being transmitted. |
Steady or Flickering Green |
Data is being transmitted. |
Receive
LED
This LED reflects when data is being received on the second serial port
(RS-232/485).
State |
Description |
Steady Off |
No power or no data being received. |
Steady or Flickering Green |
Data is being received. |
Note:
The Monitor Port
does not affect any LEDs on the RMC75.
See Also
RMC75S Wiring | Serial Overview | CPU Modules Overview (RMC75)