RMC75S CPU Module

The RMC75S combines multiple communication protocols with RS-232 and RS-485 transceiver options to form a versatile and industrial-hardened communication platform. The RS-232 option provides full-duplex point-to-point communications, while RS-485 allows half-duplex multi-drop networking with up to 128 RMC75s.

Due to limited throughput of serial communications, the RMC75S is best suited for applications where time-critical machine control functions related to motion are implemented in the RMC75S using the User Programs.  The serial communications is fine for low-bandwidth monitoring or modifications to the RMC75S parameters or User Programs. In applications where higher throughput is necessary, consider the RMC75E Ethernet module.

Features

Part Number

The part numbers of the RMC75S is RMC75S. Like all RMC75 CPU modules, the RMC75S can only be ordered with an axis module.

For example, RMC75S-QA2 is an RMC75S with a two-axis QA2 module.

Specifications

General

Weight

245 g + 16 g (connector)

Serial Interface

Transceivers

User-selectable: RS-232, RS-485

Baud Rates

9600, 19200, 38400, 57600, 115200 baud

Stop Bits

1 or 2

Data Length

8 bits

Parity

None, Odd, or Even

Isolation

500 VAC

Electrostatic Discharge (ESD) Protection

15 kV

RS-232 Interface

Type

Single-Ended

Connector

DB-9 Male

Communication Distance

50 ft (12 m)

Network Type

Point-to-Point

RS-485 Interface

Type

Differential

Connector

5-pin Terminal Block

Communication Distance

4000 ft (1200 m)

Network Type

RS-485: Point-to-Point or Multi-drop up to 128 nodes

RS-485 Input Impedance

48 kΩ (1/4 unit load)

Biasing

User selectable

Termination

120 Ω user selectable

RS-232 Monitor Port

Connector

DB-9 Male

Cable

Null modem

Protocol

Allen-Bradley DF1 Full-Duplex, with CRC error detection

Settings

38400 baud, 8 data bits, no parity, 1 stop bit, no handshaking

LEDs

Controller LED

This bi-color (red/green) LED has the following states:

State

Description

Steady Off

No power.

Steady Green

RUN Mode

Flashing Green (Slow)

PROGRAM Mode

Flashing Green (Fast)

Updating Flash or a controller restart is pending.

Flashing Red

The device is in the loader. This should occur briefly when the controller is powered up. If this occurs during normal operation, an error has occurred in the controller and it must be reset. Cycle power to the RMC75 to reset it.

Causes:

  • Power Interruption
    In certain cases, a power interruption to the RMC may cause it to go into the loader. Even a very short interruption, such as 20 msec, can cause problems. This type of interruption cannot be measured with a standard multimeter. For accurate power supply verification, use an oscilloscope or similar high-speed monitoring device.

  • Firmware Bug
    Certain firmware bugs will cause the RMC to go into the loader. If this occurs, and power interruptions have been ruled out, contact Delta Technical support.

Steady Red

Non-Recoverable major fault. That is, the module cannot boot at all, not even into the loader. The module will likely need to be shipped back to Delta for repair. Some things to try to get it into the Loader (to be done at the direction of technical support) include removing all expansion and axis modules, and setting the Force to Loader jumper under the axis module.

Communication LEDs

These LEDS are located below the Controller LED on a gray background.

Transmit LED
This LED reflects when data is being transmitted on the second serial port (RS-232/485).

State

Description

Steady Off

No power or no data being transmitted.

Steady or Flickering Green

Data is being transmitted.

 

Receive LED
This LED reflects when data is being received on the second serial port (RS-232/485).

State

Description

Steady Off

No power or no data being received.

Steady or Flickering Green

Data is being received.

 

 

Note:
The Monitor Port does not affect any LEDs on the RMC75.

 

 

See Also

RMC75S Wiring | Serial Overview | CPU Modules Overview (RMC75)