This parameter error indicates that the CONFIGURATION word has been set incorrectly. Specifically, bits 8, 9 and 10 have been set incorrectly. These bits are used to reference the pressure axis that should be assigned to the position axis. This could occur because of any of the following reasons:
There are no analog input modules installed in the RMC that have pressure control enabled. These are included in the RMC101-series products from Delta Computer Systems, Inc.
There are multiple axes trying to use the same analog axis. Each pressure axis can only be assigned to a single position axis.
The pressure axis number selected is larger than the number of pressure axes available. For example, in an RMC101-M1-A1 with the four pressure channels configured as two differential force axes, only pressure axes 0 and 1 can be selected, and attempts to access pressure axis 2 and 3 (using CONFIGURATION values of 0x0A00 and 0x0B00) will generate this error.