Mounting Options:
• Symmetrical DIN 3
• Panel-mount
Orientation:
The RMC should be mounted upright on a vertical surface, such that the air holes are on top and bottom.
Clearance above and below:
The amount of clearance required depends on the maximum ambient temperature:
Ambient Temperature |
Clearance |
122 - 140°F (50-60°C) |
3 in (7.6 cm) |
86 to 122°F (30 to 50°C)
|
2 in (5.1 cm) |
Less than 86°F (30°C) |
1 in (2.5 cm) |
Base Module:
3.22 in. x 5.0 in.
Protrudes 2.0 in. Make sure to leave room for the front connectors.
Expansion Modules
Protrude 2.0 in. Make sure to leave room for the front connectors.
D8 module 1.25 in. x 5.0 in. |
AP2, A2, Q1 modules 1.50 in. x 5.0 in. |
|
|
See Also