Mounting Options:
• Symmetrical DIN 3
• Panel-mount
Orientation:
The RMC should be mounted upright on a vertical surface, such that the air holes are on top and bottom.
Clearance above and below:
The amount of clearance required depends on the maximum ambient temperature:
|
Ambient Temperature |
Clearance |
|
122 - 140°F (50-60°C) |
3 in (7.6 cm) |
|
86 to 122°F (30 to 50°C)
|
2 in (5.1 cm) |
|
Less than 86°F (30°C) |
1 in (2.5 cm) |
The width depends on the number of slots in the backplane.
|
|
Width |
|
3 Slots |
4.10 in. |
|
4 Slots |
5.10 in. |
|
5 Slots |
6.10 in. |
|
6 Slots |
7.10 in. |
Note:
Allow space for the connectors on the front of the RMC.