PROFIBUS Module (RMC150)

The PROFIBUS module for the RMC150 provides PROFIBUS communications. Notice that since the RMC150E CPU has built-in Ethernet, it is possible to communicate via Ethernet and PROFIBUS simultaneously.

For details on setting up and using PROFIBUS, see the PROFIBUS Overview topic.

Features

Part Number

The part number of the PROFIBUS module is -PROFI. The PROFIBUS module fits only in the left-most slot of the RMC backplane.

For example, RMC150E-S1-PROFI is an RMC150E with an SSI module and a PROFIBUS module. RMC150E-S3-Q1-PROFI is an RMC150E with three SSI modules, one Quadrature module, and a PROFIBUS module.

Specifications

For general specifications on the RMC150, see the RMC150 Overview topic.

General

Weight

88 g

PROFIBUS-DP Interface

Data Rate

9.6 kbaud up to 12 Mbaud

Isolation

2500 VAC

Product Identifier Number

0x0AC6

Features Supported

Sync Mode, Freeze Mode, Auto-baud rate detect

Valid Station Addresses

0-126 (set by software or Set Slave Address function)

Connector

Standard PROFIBUS-DP DB-9 (use termination in cable connectors as per PROFIBUS specification)

LEDS

Comm Status

State

Description

Steady Off

No PROFIBUS connection is established. See the Troubleshooting PROFIBUS topic for possible reasons.

Steady Green

A PROFIBUS connection is established.

 

Note:
These are the only two LED states of the NET LED, but it is possible to have the Net LED flashing or flickering green, which indicates that the RMC75P is going on- and off-line on the PROFIBUS channel and generally indicates a network or configuration problem.

 

See Also

RMC150 Overview | PROFIBUS Overview


Send comments on this topic.

Copyright © 2024 Delta Computer Systems, Inc. dba Delta Motion