I/O Connection PLC State

Type:

Communications Register

RMC75 Address:

%MD21.24

RMC150 Address:

%MD45.24

RMC200 Address:

EtherNet/IP Connection #1: %MD112.1

EtherNet/IP Connection #2: %MD112.5

EtherNet/IP Connection #3: %MD112.9

PROFINET I/O Connection: %MD112.13

RMC75/150 System Tag:

_Enet.PLCStatus

RMC200 System Tag:

EtherNet/IP Connection #1: _Enet.IOConn1PLCState

EtherNet/IP Connection #2: _Enet.IOConn2PLCState

EtherNet/IP Connection #3: _Enet.IOConn3PLCState

PROFINET I/O Connection: _Enet.PNIOConnPLCState

How to Find:

Address Selection Tool → Controller → Communication Settings → Ethernet

Data Type:

DINT

Accessibility:

Read Only

 

These registers indicate the RUN/STOP (or RUN/PROGRAM) state of the I/O controller for EtherNet/IP and PROFINET I/O communications. For more details, see Handling Broken EtherNet/IP I/O Connections and Handling Broken PROFINET Connections.

For the RMC75 and RMC150, there is a single PLC State register shared by EtherNet/IP and PROFINET. If there is an Exclusive Owner EtherNet/IP I/O connection open, this register will reflect the state of the PLC controlling that connection. If there is a PROFINET I/O connection open, then this register will reflect the state of the I/O controller (PLC) for that connection.

For the RMC200, there is one PLC State register dedicated to each EtherNet/IP and PROFINET I/O connection.

Each register can hold one of the following three values:

Value

Description

0

Unknown
Applies when the I/O connection is not currently active.

1

RUN

2

PROGRAM or STOP

 

See Also

Handling Broken EtherNet/IP I/O Connections | Handling Broken PROFINET Connections


Send comments on this topic.