Type: |
Communications Register |
RMC75 Address: |
%MD21.11 |
RMC150 Address: |
%MD45.11 |
RMC200 Address: |
n/a (not accessible via addressing) |
System Tag: |
|
How to Find: |
Address Selection Tool → Controller → Communication Settings → Ethernet |
Data Type: |
|
Accessibility: |
Read/Write |
This register indicates the state of various Ethernet communication items.
Bit |
Tag Name |
Description |
0 |
Disable Auto-Negotiation True: Auto-Negotation is disabled. False: Use Auto-Negotation (use bits 1 and 2). |
|
1 |
100 Mbps Valid only if _Enet.Config.ManConfig is True. True: Ethernet speed is set to 100 Mpbs. False: Ethernet speed is set to 10 Mpbs. |
|
2 |
Full Duplex Valid only if _Enet.Config.ManConfig is True. True: Ethernet is set to full-duplex. False: Ethernet is set to half-duplex. |
|
3-4 |
IP Address Assignment Mode Specifies how the RMC obtains its IP address. 0: Statically Assigned 1: BOOTP 2: DHCP |
|
5 |
Lock IP Settings True: IP address settings cannot be changed via Ethernet. False: IP address settings can be changed via Ethernet. |
|
6 |
Lock Firmware Update via Ethernet True: Firmware cannot be updated via Ethernet. False: Firmware can be updated via Ethernet. |